CQT Chilled water metering status

The values shown below reflect the readings of the metering devices at the indicated date/time. Instant values reflect the temperatures/heat, the total values the accumulated values since the meter installation.

UnitDate
MM/DD/YY
Time
hh:mm:ss
Instant valuesTotal values
Thermal loadReturn TempSupply Temp CHW volumeTotal heat
AHU110/14/2506:46:0253.35 kW10.79 °C7.60 °C2464217.2 m36505724.0 kWh
AHU210/14/2506:46:0255.78 kW16.95 °C14.56 °C1912253.1 m37299862.0 kWh
AHU310/14/2506:46:0217.91 kW12.53 °C7.98 °C206790.6 m31937360.0 kWh
S14L310/14/2506:46:03169.07 kW11.36 °C4.05 °C595894.2 m33134281.0 kWh
AHU410/14/2506:46:0220.63 kW8.63 °C7.88 °C336193.9 m32565099.0 kWh
AHU510/14/2506:46:0342.65 kW11.37 °C7.30 °C280821.7 m31858099.0 kWh
AHU610/14/2506:46:030.00 kW11.98 °C9.53 °C293813.6 m32427520.0 kWh
PCW210/14/2506:46:034.72 kW10.35 °C6.58 °C84628.7 m354217.5 kWh

The total chilled water volume and removed heat refers to the time since installation of the corresponding meters. AHU1...6 refers to the heat from the air handling units in levels 1...6, PCW2 to the process water for labs 2/15, 2/16, 1/16, 1/16. Meter installation date were:

CQT Electricity metering status

Displayed values reflect the meter readings at the indicated date/time. Instant values give an idea about the consumption at this moment, the total values represent the accumulated consumption since the meter installation. New readings are available every 2 minutes.

Unit locationMeter serial Date
MM/DD/YY
Time
hh:mm:ss
Instant valuesTotal value
Voltage (V)Current (A) apparent power (kVA) active energy (kWh)
RYBRYB
MDB19452947910/14/2506:46:12240.0246.0242.765.049.070.044.645704362
E-MDB19452948010/14/2506:46:17239.8242.9242.660.356.162.143.153323871
EAHU19452948510/14/2506:46:07242.5244.9245.6 6.5 6.2 7.24.87 841608
MDB29452948110/14/2506:46:26240.3245.8243.043.020.551.027.763247562
E-MDB29452948410/14/2506:46:21239.5242.7242.815.612.4 8.28.741204832
EAHU29452948610/14/2506:46:02242.4245.0245.6 9.5 9.5 9.46.92 632719
MDB39452948210/14/2506:46:31239.9245.6242.8 2.0 2.0 5.52.31 534067
EAHU39452948710/14/2506:46:36242.4244.9245.6 2.8 3.2 3.82.41 406445
MDB3-S143875174510/14/2506:45:02198449.00.00.0 0.0 0.0 0.00.001350437
E-MDB3-S144018348110/14/2506:45:070.00.00.0 0.0 0.0 0.00.00 32571
EAHU3-S143875174210/14/2506:45:12244.9244.20.7 4.3 3.8 0.02.00 239
MDB49452948310/14/2506:46:41239.8245.4242.8 9.610.6 5.06.12 753607
EAHU49452948810/14/2506:46:46242.2245.0245.6 2.5 3.2 3.52.26 321378
MDB69982852910/14/2506:46:51239.8245.5242.5 4.4 3.2 7.23.59 495219
EAHU69982852810/14/2506:44:57241.5244.2244.6 4.3 4.7 5.03.42 298730

The apparent power is calculated via V1*I1+V2*I2+V3*I3. Missing entries are awaiting installation.

Monthly billing overview

Below is a list of the last billing cycle. The values are read off shortly (1 minute) after midnight of the 25th of each month. We also have a summary over all billing periodes for water and electricity.

Chilled water consumption for the October 2025 reading

Unit This reading
(kWh)
Last reading
(kWh)
Consumption
(kWh)
AHU16490782645714033642
AHU27280219723277547444
AHU31931619192098210637
AHU42556861253794318918
AHU51829568175990169667
AHU62418307239857219735
PCW253313.250732.62580.62
S14L330817532954590127163
Total heat dumped in chilled water: 329786.62

Measurement time interval was from 09/01/25 to 10/01/25.

Electricity consumption for the October 2025 reading

Unit This reading
(kWh)
Last reading
(kWh)
Consumption
(kWh)
EAHU18403008372263074
EAHU26306676260294638
EAHU34057754038511924
EAHU43207523193131439
EAHU62978542959651889
MDB15692465566586126604
MDB23238652321880419848
MDB35332065311392067
MDB47515437468004743
MDB64937474904663281
MDB6E3310100327919330907
MDB7E120236911975174852
Total electricity consumed: 105266

Measurement time interval was from 09/01/25 to 10/01/25.

Back to main page.